How to carry out power cable withstand voltage test?

Sep 6 | COMPANY NEWS, NEWS

  1. 1.Disconnect all electrical equipment connected to the tested cable.
  2. 2.Use a megger to test the insulation parameters of each phase of the cable, and carry out the ultra-low frequency withstand voltage test only after the test is qualified.
  3. 3.Set the test voltage value: Umax = 3uo, where uo is the rated phase voltage of the cable. Example 1: cable parameter: the rated line voltage is 10kV, and the rated phase voltage uo = 6kV, so the test voltage setting value is:

Umax = 3uo = 18kV

7水

See Table 4 for the setting value of 0.1Hz ultra-low frequency test voltage of various rubber and plastic insulated power cables.

Table 4 0.1Hz ultra-low frequency test voltage and time of various rubber plastic insulated power cables.

 Rated voltage U0/US(kV)Handover testPreventive experiment
multi pleTest voltage(kV)Test time(mins)multip leTest voltage(kV)Test time(mins)
1.8/33U05603U0515
3.6/63U011603U01115
6/63U018603U01815
6/103U018603U01815
8.7/103U026603U02615
12/203U036603U03615
21/353U063603U06315
26/353U078603U07815

Note: UN is the rated voltage of the cable, and uo is the phase voltage of the cable.

 4.Test time: 60 minutes for handover test and 15 minutes for preventive test.

 5.Setting current value of overcurrent protection:

Estimation method of capacitive current (or leakage current) of ultra-low frequency withstand

voltage test article:

Io=2πfCU=2×3.14×0.1CU(mA)

C is the electric capacity of the cable to the ground, unit: UF; u is the effective value of the test voltage, unit: kV.

Example 2: a 10KV (UN = 10kV, uo = 8.7kv) cable is 4km long, with a single phase to ground capacitance of 0.21uf/km and 0.1Hz super

If the low frequency test voltage is 26kv (peak value), the leakage current is approximately:

Io=2πfCU=2×3.14×0.1CU=0.628×0.21×4×26/  2=9.69(mA)

Setting current value of overcurrent protection: I=kIo