FEATURED PRODUCTS
Portable Crcuit Breaker Tester Switch Characteristic Tester
Short Description:
Applicable to SF6 switches, GIS switchgear, vacuum switches, oil switches, and vacuum contactors (electrically held single coil; for double coil contactors, please select the vacuum switch type). It can simultaneously measure 12 channels of metal contact breaks, 6 channels of main breaks, and 6 channels of auxiliary breaks.
Send Email To Us
Product Detail
Portable Crcuit Breaker Tester Switch Characteristic Tester Features
- Equipped with linear and rotary sensors, and a dedicated fixed multi-functional connector, installation is extremely convenient and simple. The linear sensor length can be set arbitrarily from 30-1000mm; only the sensor needs to be installed, and the instrument does not require factory program modification.
- The main unit can store 100 sets of current test data, and has an internal real-time clock for easy archiving.
- Equipped with a USB flash drive interface and an RS232 interface. Data can be saved to a USB flash drive and uploaded to a computer for analysis, storage, and printing. The RS232 interface allows for online computer connection (optional function).
- The internal anti-interference circuitry ensures reliable operation within a 500kV substation.
Portable Crcuit Breaker Tester Switch Characteristic Tester Technical parameters
| 1.Time Measurement: | 12-channel inherent opening (closing) time |
| Asynchrony within opening (closing) phases | |
| Difference in asynchrony between opening (closing) phases (1-99ms) | |
| Closing (opening) bounce time (number of bounces) | |
| Internal trigger test range: 1ms-10000ms, resolution: 0.01ms | |
| External trigger test range: 1ms-10000ms | |
| Resolution within 999ms: 0.01ms, 1000-9999ms: 0.1ms, above 10000ms: 1ms. | |
| Accuracy within 200ms: 0.05%±0.1ms | |
| 2.Speed Measurement: | Speed at initial separation (or engagement)
Average speed over a specified time period (stroke or angle segment) |
| 3.Measurement Range: | Linear sensor: 0.01~20.00m/s, accuracy ±0.1m/s |
| 345° angle sensor: 0.01~20.00m/s, accuracy ±0.1m/s | |
| 4.Stroke Measurement: | Moving contact stroke (stroke) |
| Contact stroke (opening distance) | |
| Overtravel | |
| Overshoot or rebound stroke | |
| 5.Measurement Range: | Linear sensor: 50mm, measurement range: 0-50mm, resolution 0.1mm.Optional linear sensor of any length from 100-1000mm. |
| Rotary sensor: 345° rotary sensor, measurement range: 0-1000mm, resolution 0.08°. Accuracy ± (1%L + 0.2) mm | |
| 6.Current and Resistance Range: | Maximum current 20A, resolution: 0.01A; resistance 1000Ω, resolution: 0.01Ω. Accuracy ± 5%. |
| 7.Instrument Power Supply: | AC 220V ± 10%; 50Hz ± 10% |
| 8.DC Power Output | DC20~270V continuously adjustable, instantaneous maximum current 30A, power 3300W. |
| 9.External trigger voltage: | AC/DC 10-300V, current ≤120A |
| 10.Measurement range of disconnecting switch or energy storage circuit breaker: | ⑴ Voltage output: DC 20~270V (adjustable); |
| ⑵ Power output time: 0.01-10 seconds (adjustable); | |
| ⑶ Maximum acquisition time of disconnection signal: 10 seconds; | |
| ⑷ Measurable disconnection closing and opening time, three-phase asynchrony, bounce time and number of times | |
| 11.Main unit dimensions: | 360×260×170mm |
| 12.Operating environment: | -20℃~+50℃ |
| 13.Relative humidity: | ≤90% |